About the Product

Honeywell FS-TSFIRE-1624 Safe Fire Detector Input FTA

The FS-TSFIRE-1624 from Honeywell is a critical safety interface for fire detection systems. This Field Termination Assembly provides 16-channel fire detector connectivity with advanced line monitoring. It serves hazardous locations with reliable performance in emergency situations.

Product Overview

  • The FS-TSFIRE-1624 connects digital fire detectors to Safety Manager systems.
  • It interfaces directly with safe high-density analog input modules.
  • Voltage-current-limited power supply meets Class I Division 2 requirements.
  • Global reset function allows coordinated reset of all connected sensors.
  • Universal DIN rail mounting simplifies installation in control panels.
  • Secure screw terminals ensure dependable field wiring connections.

Technical Specifications

  • Brand: Honeywell
  • Model: FS-TSFIRE-1624
  • Input Channels: 16 independent fire detector inputs
  • Operating Voltage: 24V DC external supply
  • Voltage Range: +25% / -15% tolerance
  • Current Draw: 570 mA maximum with EOL resistors
  • Channel Resistance: 680 Ω ±5% per channel
  • Input Voltage: 20.5 V DC typical with EOL resistor
  • Shorted Current: 35 mA maximum at 24V DC
  • Relay Current: 8.5 mA typical at 24V DC
  • Weight:0.63kg

Installation Details

  • Compact dimensions: 170 × 70 × 64 mm
  • DIN rail compatible: TS32 / TS35 × 7.5
  • Required rail length: 171 mm
  • Maximum wire size: 2.5 mm² (AWG 14)
  • Strip length: 7 mm for proper termination
  • Terminal torque: 0.5 Nm for secure connections

Safety and Field Specifications

  • Certified for Class I, Division 2 hazardous locations
  • Maximum field wire resistance: < 100 Ω
  • End-of-Line resistor: 4.7kΩ ±5% (0.25 W typical)
  • Hydrogen groups A&B: 60 mH inductance, 0.3 µF capacitance
  • Non-hydrogen groups C&D: 230 mH inductance, 7 µF capacitance
  • Line monitoring ensures continuous circuit integrity
  • Multiple international safety certifications included

Packaging and Shipping

  • Includes one FS-TSFIRE-1624 FTA module
  • Industrial-grade protective packaging
  • Global shipping via FedEx, UPS, and DHL
  • Fast delivery for urgent safety system requirements

Frequently Asked Questions

  • How many fire detectors can connect to this module?
    The module supports sixteen individual fire detector connections.
  • What is the line monitoring feature?
    It continuously monitors circuit integrity for reliable fire detection.
  • What power supply is needed?
    It requires a 24V DC external power supply with +25%/-15% tolerance.
  • Can I reset all sensors simultaneously?
    Yes, the global reset function resets all connected fire detectors.
  • What environment is this module designed for?
    It is certified for Class I, Division 2 hazardous locations.
  • Quick Quotes: Receive pricing and availability fast from our dedicated customer service team.
  • Delivery: Expedited, freight, and international shipping available worldwide.
  • Warranty: NexAuto offers a 12-month warranty on all parts purchased from us, in addition to any manufacturer coverage.
  • Returns: 30-day return policy for defective or mismatched parts, ensuring peace of mind.
  • Payment: Flexible options including major credit cards, PayPal, and bank transfers.
  • Custom Calibration: Provide your specifications, and we’ll handle the rest with precision.
Vollständige Details anzeigen