Honeywell MU-PAIL02 Low Level Analog Input - 8 Ch

Bulk Orders & Fast Shipping

Instant 10% Discount On Winter Banks Credit/Debit Cards EMI and CreditCard

Fast & Reliable Worldwide Shipping – Ready to Dispatch from Stock

In stock (16 units), ready to be shipped
  • Fast shipping
  • Return Policy
  • Lowest Price
  • Help Center 24/7

About the Product

Honeywell MU-PAIL02 Low Level Analog Input Processor

Key Technical Specifications

  • Brand & Model: Honeywell MU-PAIL02 (Low Level Analog Input Processor - 8 Inputs)
  • Input Type: Thermocouple, RTD, Voltage, and Current
  • Input Channels: 8 galvanically isolated
  • A/D Converter Resolution: 15 bits
  • Common Mode Voltage (CMV): 250 Vac rms or ±250 Vdc
  • Dielectric Strength: 1500 Vac rms or ±1500 Vdc
  • CMRR (dc to 60 Hz): ≥120 dB min. with 1k lead imbalance
  • NMRR (at line frequency): ≥60 dB min.
  • Normal Mode Filter Response: -3 dB point: 10.6 Hz typical (range 9.6~11.9 Hz)
  • Crosstalk (dc to 60 Hz): ≥120 dB
  • Input Impedance: 5 kΩ min. (unpowered) / 10 MΩ min. (powered) @ 0-5V
  • Max Normal Mode Input (no damage): -20 mV to 5.5V
  • Input Scan Rate: 8 samples/sec/channel (simultaneous); 4 samples/sec/channel (TC open detection)
  • Line Frequency Sync Range: 50/60 Hz +3%, -6% (hardware only)
  • Hardware Accuracy (0-100mV, 0-5V): ±0.05% of full scale or ±0.075% of reading (whichever larger) @23.5±2°C
  • Software Accuracy (Thermocouple): ±0.1°C typical, ±0.5°C max @23.5±2°C
  • Reference Junction Accuracy: ±0.9°C max @23.5±2°C (in cabinet)
  • Temp Stability (Voltage/Current/TC): 45 ppm/°C RSS
  • Temp Stability (RTD Input): 50 ppm/°C RSS (85 ppm/°C maximum)
  • Surge Withstand Capability: Complies with ANSI/IEEE C37.90.1-1978 (common mode)

Frequently Asked Questions (FAQ)

  • Q: Can the Honeywell MU-PAIL02 connect directly to a 2-wire transmitter?
    A: Yes, but the transmitter needs an external power supply. The module only provides the input interface.
  • Q: How does open thermocouple detection affect the sampling rate?
    A: Enabling this feature reduces the scan rate from 8 to 4 samples per second per channel.
  • Q: What are the CMV and dielectric withstand ratings for the MU-PAIL02?
    A: CMV is 250 Vac rms or ±250 Vdc; dielectric withstand is 1500 Vac rms or ±1500 Vdc.
  • Q: What happens if the input exceeds -20mV to 5.5V?
    A: Exceeding this range may damage the module. Always keep signals within this limit.
  • Q: What is the difference between hardware and software accuracy?
    A: Hardware accuracy applies to voltage/current inputs; software accuracy refers to thermocouple temperature conversion error.
  • Q: Does the MU-PAIL02 support both 50Hz and 60Hz line synchronization?
    A: Yes, it covers a range of +3% to -6% for both frequencies via hardware synchronization.

© 2026 NexAuto Technology Limited. All rights reserved.
Original Source: https://www.nex-auto.com/
Contact: sales@nex-auto.com
Phone: +86 153 9242 9628

  • Quick Quotes: Receive pricing and availability fast from our dedicated customer service team.
  • Delivery: Expedited, freight, and international shipping available worldwide.
  • Warranty: NexAuto offers a 12-month warranty on all parts purchased from us, in addition to any manufacturer coverage.
  • Returns: 30-day return policy for defective or mismatched parts, ensuring peace of mind.
  • Payment: Flexible options including major credit cards, PayPal, and bank transfers.
  • Custom Calibration: Provide your specifications, and we’ll handle the rest with precision.